Spinal Cord Injury Center Design Guide
July 1990 (Rev. Jan. 2004)
Two-Bed Room 2
Function:
This space is intended primarily to accommodate those patients who do not require acute care, and to
provide a more private atmosphere for those capable of independent care. It also provides flexibility in
room assignments allowing the pairing of females or patients with the same infection.
Space Requirement:
415 NSF
Architectural:
Finish Code:
1A
Floor Finish:
Base:
Vinyl
Wall Finish:
Gypsum Wallboard*
Ceiling:
Acoustical Tile
Ceiling Height:
9'-0" (8' w/wall-mount TV)
Noise (STC Rating):
35
Slab Depression:
None
Special Construction: -
Hardware:
7
Doors:
4'-0" x 7'-0" wood or metal, optional view glass panel.
Windows:
Required by code, operable, see PG-18-3, Topic 1, Codes and Standards.
*Vinyl Wallcovering at Lavoratory
HVAC:
Temperature:
Summer: 72@50%RH
Winter:
82@30%RH
Min. Air Changes/Hour: None (see HVAC Note 3)
Min. % Outside Air:
15%
Pressure:
(0)
% Filtration:
30%(PF)/85%(AF)
Noise Criteria:
35
A/C Loads:
Lights:
900w
Equipment: 1050w
People:
260w, sensible
220w, latent
Electrical:
Lighting Levels:
Gen. Illum: 10fc
Task Illum: 70fc
Over Bed: 30fc
Emergency Power:
Medical Gasses
Night Lights
Vanity Light
One Receptacle per PBPU
Nurse Call
Office of Facilities Management
38