Spinal Cord Injury Center Design Guide
July 1990 (Rev. Jan. 2004)
Anteroom 1-A
Function:
This space is intended to provide an airlock between the Isolation Room and the Nursing Unit Corridor,
and to accommodate proper isolation technique.
Space Requirement:
50 NSF; add 30 NSF if nurse-servers are required.
Architectural:
Finish Code:
1-A
Floor Finish:
Base:
Vinyl
Wall Finish:
Gypsum Wallboard/Paint*
Ceiling:
Acoustical Tile
Ceiling Height:
8'-0"
Noise (STC Rating):
35
Slab Depression:
None
Special Construction: -
Hardware:
12, both doors
Doors:
3'-6" x & 7'-0" gasketed wood or metal, optional view glass panel at corridor.
Windows:
Observation window into Isolation Room, SD 08110-4.DWG.
*Vinyl Wallcovering at Lavoratory
HVAC:
Temperature:
Summer: 72@50%RH
Winter:
82@30%RH
Min. Air Changes/Hour: 6, 100% Exhaust
HEPA Filters
Min. % Outside Air:
15%
Pressure:
(+) or (-), see SD 15902-13.DWG and 15902-14.DWG
% Filtration:
30%(PF)/85%(AF)
Noise Criteria:
35
A/C Loads:
Lights:
75w
Equipment: 150w
People:
65w, sensible
55w, latent
Electrical:
Lighting Levels:
Gen. Illum: 30fc
Emergency Power:
One Receptacle
Ventilation
Office of Facilities Management
35