Final Draft 12-31-95
Revised May 1997
Equipment Guide List
Automated Radiographic Room
SYMBOL
QTY AI
DESCRIPTION
NOTE: PROVIDE PIPING CONNECTION FROM PROCESSORS TO SILVER RECOVERY
SYSTEM, IF REQUIRED.
NOTE: SERVICES, ELECTRICAL, AS REQUIRED FOR EQUIPMENT
NOTE: PROVIDE ONLY WHEN APPROVED FOR A SPECIFIC PROJECT (OXYGEN, AIR,
VACUUM OUTLET AND BRACKET)
NOTE: OUTLET, WALL, MEDICAL AIR (PG-18-1, MCS 15491)
NOTE: OUTLET, WALL, OXYGEN (PG-18-1, MCS 15491)
NOTE: OUTLET, WALL, VACUUM (PG-18-1, MCS 15491)
NOTE: CONNECTIONS, PLUMBING, ELECTRICAL OR MECHANICAL AS REQUIRED
NOTE: FLOOR DRAIN, NEAR FILM PROCESSING UNITS (PLUMBING DESIGN CRITERIA AND
INSTRUCTIONS)
NOTE: FLOOR DRAIN, NEAR REPLENISHER TANK UNITS (PLUMBING DESIGN CRITERIA &
INSTRUCTIONS)
NOTE: LOW LEVEL DIMMED INCANDESCENT LIGHTING SYSTEM IN ADDITION TO GENERAL
NOTE: SHIELDING, RADIATION, FOR ROOMS WITH
FIXED X-RAY EQUIPMENT, IN
ACCORDANCE WITH PG-18-1, MCS 13091; PG-18-4, SD 24 THRU 24K AND NCRP REPORT
NO. 33, 35 AND 49)
AR
CC
COUNTERTOP, PLASTIC LAMINATE, FIXED, WALL MOUNTED,
760mm (30") ABOVE FINISHED FLOOR, APPROX., 1525mm x
457mm (60" x 18"), PROVIDE UNDER ILLUMINATOR
(PG-18-1, MCS 12302)
1
CC
DISPENSER, SOAP, WALL MOUNTED WITH FOOT CONTROL
(PG18-1, MCS 10800)
P-802
1
CC
HOSE BIBB, COMBINATION FAUCET, WALL MOUNTED,
CONCEALED SUPPLY PIPES
(PG-18-1, MCS 15450, PG-08-4, SD VOL. 3 SD 380)
P-418
1
CC
LAVATORY, SENSOR CONTROL
(PG-18-1, MCS 15450; VOL. 3 SD 380)
1
CF
CABINET, FOR EQUIPMENT MANUAL, WALL MOUNTED, APPROX.,
1220mm x 405mm x 405mm (48" x 16" x 16")
1
CF
CABINET, STORAGE, WALL MOUNTED, 255mm (10") ABOVE
FINISHED FLOOR, 5 SHELVES AND FOLDING DOOR, APPROX.
610mm x 405mm x 1575mm (24" x 16" x 62")
VA DESIGN GUIDE
RADIOLOGY SERVICE
PAGE 4-8