Final Draft 12-31-95
Revised May 1997
Design Standards
Mammography Room
ARCHITECTURAL
CONDITIONING
Ceiling:
Ceiling Ht:
2700 mm (9'-0")
Dry Bulb Temp Cooling:
25C (78F)
Wall Finish:
--
22C (72F)
Wainscot:
--
Minimum % Outside Air:
15%
Base:
Resilient base
--
Floor Finish:
Noise Criteria:
NC-40
Slab Depr:
--
Steam:
--
Notes: 1. 1100 mm (3'-8") wide door
Relative Humidity/Cooling:
50%
Relative Humidity/Heating:
30%
Minimum Air Changes/Hr.:
4
SPECIAL EQUIPMENT
Room Pressure:
0
None
AC Load-Equipment:
54 W/sm (5W/sf)
AC Load Lighting:
22 W/sm (2 W/sf)
LIGHTING
Number of People:
3
General:
30 FC
--
Special:
--
Notes:
--
Notes: 1. 600 mm x 1200 mm (2' x 4')
PLUMBING AND MEDICAL GASES
acrylic prismatic lens, W/3-F32T8
Cold Water:
Yes
lamps, 3500 deg. K, CRI=75.
Hot Water:
Yes
Laboratory Air:
--
POWER
Laboratory Vacuum:
--
Sanitary Drain:
Yes
General:
Reagent Grade Water:
--
Emergency:
--
Medical Air:
--
Notes:
--
Medical Vacuum:
--
Oxygen:
--
COMMUNICATION
Notes:
ADP:
--
Radio:
--
Telephone:
Yes
Intercom:
--
Pub. Addr:
--
Notes:
--
VA DESIGN GUIDE
RADIOLOGY SERVICE
PAGE 4-7