FINAL DRAFT 9-26-95
REVISED FEBRUARY 1997
Scope Cleaning/Clean Storage
Design Standards
ARCHITECTURAL
Ceiling:
Acoustical ceiling tile
ADP:
---
Ceiling Ht:
2700 mm (9'-0")
Radio:
---
Wall Finish:
High build glazed coating
Telephone:
Yes
Wainscot:
---
Intercom:
---
Base:
Integral welded seam
Public Addr:
---
Floor Finish:
Welded seam sheet flooring
Notes:
---
Slab Depr:
---
Notes:
1. 900 mm (3'-0") wide doors
CONDITIONING
with tempered glass view
windows.
Dry Bulb Temp Cooling:
25 0 C (78 0 F)
22 0 C (72 0 F)
SPECIAL EQUIPMENT
Minimum % Outside Air:
---
None
100%Exhaust Air:
Yes
Noise Criteria:
NC 40
ELECTRICAL
Steam:
---
General:
30 FC
Relative Humidity/Cooling:
50%
Special:
---
Relative Humidity/Heating:
30%
Notes:
1.600 mm x 1200 mm
Minimum Air Changes/Hr.: 10- scope cleaning
4 clean storage
fluorescent light fixtures,
Room Pressure: Negative for scope cleaning
acrylic prismatic lens,
W/2-F32T8 lamps,
positive for clean storage
3500k, CRI=75 (min.)
AC Load-Equipment:
scope cleaning 54 W/sm (5 W/sf)
POWER
clean storage
22 W/sm (2W/sf)
General:
AC Load-Lighting:
Emergency:
---
scope cleaning
13W/sm (1.2W/sf)
Notes:
1.Special receptacle for
clean storage
19W/sf (1.8W/sf)
endoscope washer,
Number of People:
3 per room
coordinate with supplier.
---
Notes:
1.Provide counter to
room.
VA DESIGN GUIDE
PULMONARY MEDICINE SERVICE
PLATE 6-2