FINAL DRAFT 9-26-95
REVISED FEBRUARY 1997
Equipment Room Storage/Supply/Clean-up/Repair/Testing
Design Standards
ARCHITECTURAL
Ceiling:
Acoustical ceiling tile
ADP:
---
Ceiling Ht:
2700 mm (9'-0")
Radio:
---
Wall Finish:
Paint
Telephone:
Yes
Wainscot:
---
Intercom:
---
Base:
Resilient Base
Public Addr:
---
Floor Finish:
Notes:
---
Slab Depr:
---
Notes:
1.
1120 mm (3'-8" ) wide
doors with tempered
CONDITIONING
glass view windows.
25 0 C (78 0 F)
Dry Bulb Temp Cooling:
0
0
22 C (72 F)
SPECIAL EQUIPMENT
Minimum % Outside Air:
15%
None
For clean-up room only
Noise Criteria:
NC-40
ELECTRICAL
Steam:
---
General:
20 FC
Relative Humidity/Cooling:
50%
storage/supply:
50 FC
Relative Humidity/Heating:
30%
clean-up/repair:
30 FC
Minimum Air Changes/Hr.: 10-clean-up room
equipment storage:
20 FC
4 for all others
Notes:
1. 600 mm x 1200 mm (2' x 4')
Room Pressure:
Negative
fixtures, acrylic prismatic
AC Load-Equipment:
32 W/sm (3 W/sf)
lens, W/2-F32T8 lamps,
AC Load-Lighting:
3500k, CRI=75 (minimum)
(A)storage:
11 W/sm ( 1 W/sf)
(B)clean-up:
27 W/sm (2.5 W/sf)
POWER
(C)equip./storage: 29 W/sm (2.7 Wsf)
General:
Number of People:
3 per room
Emergency:
---
Special Exhaust:
---
Notes:
---
Notes:
for clean-up/repair room
VA DESIGN GUIDE
PULMONARY MEDICINE SERVICE
PLATE 6-1