Final Draft 11-30-95
Revised March 1997
Design Standards
Drug Information Service
ARCHITECTURAL
CONDITIONING
Ceiling:
Ceiling Ht:
2740 MM (9'-0")
Dry Bulb Temp Cooling:
22C (72F)
Wall Finish:
Painted Gypsum Wallboard
22C (72F)
Wainscot:
--
Minimum % Outside Air:
15
Base:
Resilient base
--
Noise Criteria:
NC-40
Slab Depr:
--
Steam:
--
Notes:
--
Relative Humidity/Cooling:
50%
Relative Humidity/Heating:
30%
SPECIAL EQUIPMENT
Minimum Air Changes/Hr.:
4
Room Pressure:
0
None
AC Load Lighting:
32 w/sm (3 w/sf)
LIGHTING
AC Load-Equipment:
54 w/sm (5 w/sf)
Number of People:
3
General:
75 FC (ambient)
--
Special:
--
Notes:
--
Notes:
1. Dual-level switching provided
50/10 FC levels.
PLUMBING AND MEDICAL GASES
fluorescent light fixture, acrylic
Cold Water:
--
prismatic lens, W/2-F32T8
Hot Water:
--
lamps, 3500K, CRI=75 (Min.).
Laboratory Air:
--
Laboratory Vacuum:
--
Sanitary Drain:
--
POWER
Reagent Grade Water:
--
General:
Medical Air:
--
Emergency:
--
Medical Vacuum:
--
Notes:
--
Oxygen:
--
Notes:
--
COMMUNICATION
ADP:
Yes
Radio:
--
Telephone:
Yes
Intercom:
--
Pub. Addr:
--
Notes:
--
VA DESIGN GUIDE
PHARMACY SERVICE
PAGE 6-1