Final Draft 11-30-95
Revised March 1997
Design Standards
Dispensing
ARCHITECTURAL
CONDITIONING
Ceiling:
Ceiling Ht:
2740 mm (9'-0")
Dry Bulb Temp Cooling:
22C (72F)
Wall Finish:
Painted Gypsum Wallboard on
22C (72F)
reinforced masonry sub-wall.
Minimum % Outside Air:
15
Wainscot:
--
--
Base:
Resilient base
Noise Criteria:
NC-40
Floor Finish:
Carpet
Steam:
--
Slab Depr:
--
Relative Humidity/Cooling:
50%
Notes: 1. Refer to VA Construction
Relative Humidity/Heating:
30%
Standard CD-49 for security
Minimum Air Changes/Hr.:
4
criteria
Room Pressure:
0
AC Load Lighting:
32 w/sm (3 w/sf)
SPECIAL EQUIPMENT
AC Load-Equipment:
54 w/hr (5 w/hr)
Number of People:
3
None
--
LIGHTING
Notes:
General:
100 FC
PLUMBING AND MEDICAL GASES
Special:
--
Notes: 1. Lighting controlled by area;
Cold Water:
--
switch(es) located at room
Hot Water:
--
entrance.
Laboratory Air:
--
Laboratory Vacuum:
--
fluorescent light fixture, acrylic
Sanitary Drain:
--
prismatic lens, W/3-F32T8 lamps,
Reagent Grade Water:
--
4100K, CRI=85 (Minimum)
Medical Air:
--
Medical Vacuum:
--
POWER
Oxygen:
--
Notes:
General:
Emergency:
--
Notes:
1. Junction box for 120V power
connection to electronic tablet
counting machine.
2. Junction box(es) for 120V
power and signal connections to
patient notification monitor.
COMMUNICATION
ADP:
Yes
Radio:
--
Telephone:
Yes
Intercom:
--
Pub. Addr
--
Notes:
1. Conduit and junction boxes
required for patient notification
monitor system.
VA DESIGN GUIDE
PHARMACY SERVICE
PAGE 5-3