Final Draft 11-30-95
Revised March 1997
Design Standards
Extemporaneous Repackaging & Extemporanous
Compounding
ARCHITECTURAL
CONDITIONING
Ceiling:
Ceiling Ht:
2740 mm (9'-0")
Dry Bulb Temp Cooling:
22C (72F)
Wall Finish:
Painted Gypsum Wallboard
22C (72F)
Wainscot:
--
Minimum % Outside Air:
15
Base:
Resilient Base
--
Noise Criteria:
NC-40
Slab Depr:
--
Steam:
--
Notes:
--
Relative Humidity/Cooling:
50%
Relative Humidity/Heating:
30%
SPECIAL EQUIPMENT
Minimum Air Changes/Hr.:
4
Room Pressure:
0
None
AC Load Lighting:
32 w/sm (3 w/sf)
LIGHTING
AC Load Equipment:
64 w/sm (5 w/sf)
Number of People:
3
General:
100 FC
--
Special:
--
Notes:
Notes:
1.Lighting control by area;
switch(es) at room entrance.
PLUMBING AND MEDICAL GASES
fluorescent light fixture, acrylic
Cold Water:
Yes
prismatic lens, W/3-F32T8 lamps,
Hot Water:
Yes
3500 K CRI=75 (Min.).
Laboratory Air:
--
Laboratory Vacuum:
--
POWER
Sanitary Drain:
--
Reagent Grade Water:
Yes
General:
Medical Air:
--
strip mold on modular casework)
Medical Vacuum:
--
Emergency:
--
Oxygen:
--
Notes:
1. Junction box for 120V power
Notes: 1. Drain and vent need to be
connection to electrical strip mold
chemical resistant type.
on modular casework
2. Junction box for 120V power
connection to tablet and capsule
counting machine.
3. Junction box for 120V power
connection to unit dose packer
machine.
ADP:
--
Radio:
--
Telephone:
Yes
Intercom:
--
Pub. Addr:
--
Notes:
via modular casework utility
access lab module to outlets on
casework.
VA DESIGN GUIDE
PHARMACY SERVICE
PAGE 4 - 5