Final Draft 11-30-95
Revised March 1997
Design Standards
Receiving Area
ARCHITECTURAL
CONDITIONING
Ceiling:
Ceiling Ht:
2740 mm (9'-0")
Dry Bulb Temp Cooling:
22C (72F)
Wall Finish:
Painted Gypsum Wallboard
22C (72F)
Wainscot:
--
Minimum % Outside Air:
15
Base:
Resilient base
--
Floor Finish:
Noise Criteria:
NC-40
Slab Depr:
--
Steam:
--
Notes: 1. 1120mm (3'-8") Wide Door
Relative Humidity/Cooling:
50%
Relative Humidity/Heating:
30%
SPECIAL EQUIPMENT
Minimum Air Changes/Hr.:
4
Room Pressure:
0
None
AC Load Lighting:
13 w/sm (1.2 W/sf)
LIGHTING
AC Load Equipment:
32 w/sm (3W/sf)
Number of People:
6
General:
30 FC
--
Special:
--
Notes:
--
Notes: 1. Lighting control by area; switching
PLUMBING AND MEDICAL GASES
fluorescent light fixture, acrylic
prismatic lens, W/2-F32T8 lamps,
Cold Water:
--
3500 K CRI=75 (minimum)
Hot Water:
--
Laboratory Air:
--
POWER
Laboratory Vacuum:
--
Sanitary Drain:
--
General:
Reagent Grade Water:
--
Emergency:
--
Medical Air:
--
Notes:
--
Medical Vacuum:
--
Oxygen:
--
Notes:
--
ADP:
Yes
Radio:
--
Telephone:
Yes
Intercom:
--
Pub. Addr:
--
Notes:
--
VA DESIGN GUIDE
PHARMACY SERVICE
PAGE 4 - 4