Final Draft 11-30-95
Revised March 1997
Design Standards
ARCHITECTURAL
CONDITIONING
Ceiling:
Ceiling Ht:
2740 mm (9'-0")
Dry Bulb Temp Cooling:
22C (72F)
Wall Finish:
Painted Gypsum Wallboard
22C (72F)
Wainscot:
--
Minimum % Outside Air:
15
Base:
Resilient base
--
Noise Criteria:
NC-40
Slab Depr:
--
Steam:
--
Notes:
Relative Humidity/Cooling:
50%
Relative Humidity/Heating:
30%
SPECIAL EQUIPMENT
Minimum Air Changes/Hr.:
4
Room Pressure:
0
This space will have immediate access to a
AC Load Lighting:
18 w/sm (1.7 w/sf)
material transport system.
AC Load Equipment:
54 w/sm (5 w/hr)
LIGHTING
Number of People:
3
--
General:
50 FC
Notes:
Special:
--
Notes: 1. Lighting control by area;
PLUMBING AND MEDICAL GASES
switch(es) at room entrance.
Cold Water:
--
fluorescent light fixture, acrylic
Hot Water:
--
prismatic lens, W/2-F32T8 lamps,
Laboratory Air:
--
3500 K CRI=75 (Min.)
Laboratory Vacuum:
--
Sanitary Drain:
--
POWER
Reagent Grade Water:
--
Medical Air:
--
General:
Medical Vacuum:
--
strip mold on modular casework)
Oxygen:
--
Emergency:
--
Notes:
Notes: 1. Junction box for 120V power
connection to electrical strip mold
on modular casework
ADP:
Yes
Radio:
--
Telephone:
Yes
Intercom:
--
Pub. Addr:
--
via modular casework utility
access module to outlets on
casework.
VA DESIGN GUIDE
PHARMACY SERVICE
PAGE 4 - 2