Final Draft 11-30-95
Revised March 1997
Design Standards
Unit Dose and Ward Stock
ARCHITECTURAL
CONDITIONING
Ceiling:
Ceiling Ht:
2740 mm (9'-0")
Dry Bulb Temp Cooling:
22C (72F)
Wall Finish:
Paint
22C (72F)
Wainscot:
--
Minimum % Outside Air:
15
Base:
Resilient base
--
Floor Finish:
Noise Criteria:
NC-35
Slab Depr:
--
Steam:
--
Notes:
Relative Humidity/Cooling:
50%
Relative Humidity/Heating:
30%
SPECIAL EQUIPMENT
Minimum Air Changes/Hr.:
4
Room Pressure:
0
None
AC Load Equipment:
54 w/sm (5W/SF)
LIGHTING
AC Load Lighting:
32 w/sm (3 W/SF)
Number of People:
3
General:
100 FC
--
Special:
--
Notes:
Notes: 1. Lighting control by area;
switch(es) at room entrance.
PLUMBING AND MEDICAL GASES
fluorescent light fixture, acrylic
Cold Water:
--
prismatic lens, W/2-F32T8 lamps,
Hot Water:
--
3500 K CRI=75 (minimum)
Laboratory Air:
--
Laboratory Vacuum:
--
POWER
Sanitary Drain:
--
Reagent Grade Water:
--
General:
Medical Air:
--
strip mold on modular casework)
Medical Vacuum:
--
Emergency:
--
Oxygen:
--
Notes:
1. Junction box for 120V power
Notes:
connection to electrical strip mold
on modular casework
2. Junction box for dose dispensing
machine to be ceiling-mounted
ADP:
Yes
Radio:
--
Telephone:
Yes
Intercom:
--
Pub. Addr:
--
Notes:
via modular casework utility
access module to outlets on
casework.
VA DESIGN GUIDE
PHARMACY SERVICE
PAGE 4 - 1