First Draft 8-14-96
Revised June 97
Design Standards
Filing and Assembly
ARCHITECTURAL
CONDITIONING
Ceiling:
Ceiling Ht:
2740 mm (9'-0")
Dry Bulb Temp Cooling:
22C (72F)
Wall Finish:
Painted Gypsum Wallboard
22C (72F)
Wainscot:
--
Minimum % Outside Air:
15
Base:
Resilient base
--
Floor Finish:
Carpet
Noise Criteria:
NC-35
Slab Depr:
--
Steam:
--
Notes:
--
Relative Humidity/Cooling:
50%
Relative Humidity/Heating:
30%
SPECIAL EQUIPMENT
Minimum Air Changes/Hr.:
4
Room Pressure:
0
None
AC Load Lighting:
43 w/sm (4 w/sf)
AC Load-Equipment:
32 w/sm (3 w/sf)
LIGHTING
Number of People:
2
General:
4 w/sf 1076 lx (100 FC)
--
Special:
--
Notes:
Notes: 1. Lighting controlled by area with
switch(es) at room entrance.
PLUMBING AND MEDICAL GASES
2. 600mm x 1200mm (2' x 4')
Cold Water:
--
Hot Water:
--
parabolic louver lens, w/3-F32T8
Laboratory Air:
--
lamps, 3500k, CRI=75
Laboratory Vacuum:
--
(minimum)
Sanitary Drain:
--
3. Coordinate height of rotary file
Reagent Grade Water:
--
with lighting layout.
Medical Air:
--
Medical Vacuum:
--
POWER
Oxygen:
--
General:
Notes:
Emergency:
--
Notes: 1. Junction box for 120V power
connection to electric rotary file
COMMUNICATION
ADP:
--
Radio:
--
Telephone:
Yes
Intercom:
--
Pub. Addr:
--
Notes:
--
VA DESIGN PRIMER
OUTPATIENT PHARMACY