First Draft 8-14-96
Revised June 97
Design Standards
Prescription Receiving
ARCHITECTURAL
CONDITIONING
Ceiling:
Ceiling Ht:
2740 mm (9'-0")
Dry Bulb Temp Cooling:
22C (72F)
Wall Finish:
Fabric (Tackboard Wall Surface)
22C (72F)
Wainscot:
--
Minimum % Outside Air:
15
Base:
Resilient base
--
Floor Finish:
Carpet
Noise Criteria:
NC-35
Slab Depr:
--
Steam:
--
Notes:
Relative Humidity/Cooling:
50%
Relative Humidity/Heating:
30%
SPECIAL EQUIPMENT
Minimum Air Changes/Hr.:
4
Room Pressure:
0
None
AC Load Lighting:
18 w/sm (1.7 w/sf)
AC Load-Equipment:
46 w/sm (4.3w/sf)
LIGHTING
Number of People:
3
General:
1.7 w/sf 538 lx (50 FC)
--
Special:
--
Notes:
Notes: 1. Single switch per station controls
station lighting. As an alternate,
PLUMBING AND MEDICAL GASES
lighting may be controlled by area
Cold Water:
--
with switch(es) located at room
Hot Water:
--
entrance.
Laboratory Air:
--
2. 600mm x 1200mm (2' x 4')
Laboratory Vacuum:
--
Sanitary Drain:
--
parabolic louver, W/3-F32T8
Reagent Grade Water:
--
lamps, 3500K, CRI=75
Medical Air:
--
(minimum)
Medical Vacuum:
--
Oxygen:
--
POWER
Notes:
--
General:
Emergency:
--
Notes:
COMMUNICATION
ADP:
Yes
Radio:
--
Telephone:
Yes
Intercom:
--
Pub. Addr:
--
Notes:
1. Nurse Call/Code One/EMS
recorder.
VA DESIGN PRIMER
OUTPATIENT PHARMACY
PAGE 3-1