FINAL DRAFT 9/6/95
UPDATED NOV. 1996
Design Standards
Employee Biosafety Room - Toilet and Lockers
ARCHITECTURAL
CONDITIONING
Ceiling:
Acoustical ceiling tile
0
0
Ceiling Ht:
2740 mm (9'-0")
Dry Bulb Temp Cooling:
25 C (78 F)
0
0
Wall Finish:
Ceramic tile
22 C (72 F)
Wainscot:
---
Minimum % Outside Air:
---
Base:
Ceramic tile
Yes
Floor Finish:
Ceramic tile
Noise Criteria:
NC-40
Slab Depr.:
---
Steam:
---
Notes:
Plaster ceiling in shower
Relative Humidity/Cooling:
50%
Relative Humidity/Heating:
30%
SPECIAL EQUIPMENT
Minimum Air Changes/Hr.:
10
Room Pressure:
Negative
---
11 w/m 2(1 w/sf)
AC Load-Equipment:
2
ELECTRICAL LIGHTING
AC Load Lighting
11 w/m (1 w/sf)
General:
30FC
Number of People:
6-8
---
Notes:
1.
600 mm x 1200 mm (2' x
Notes:
---
fixtures, acrylic prismatic lens,
PLUMBING AND MEDICAL GAS
W/2-=F32T8 lamps, 4100 deg.
k, CRI-85 (minimum).
Cold Water:
Yes
Hot Water:
Yes
POWER
Laboratory Air:
---
Laboratory Vacuum:
---
General:
Sanitary Drain:
---
on electrical strip mold
Reagent Grade Water:
---
on modular casework)
Medical Air:
---
Emergency:
---
Medical Vacuum:
---
Notes:
---
Oxygen:
---
Notes:
---
ADP:
---
Radio:
---
Telephone:
Yes
Intercom:
---
Public Addr:
Yes
Notes:
---
VA DESIGN GUIDE
NUCLEAR MEDICINE SERVICE
5-5