FINAL DRAFT 9/6/95
UPDATED NOV. 1996
Design Standards
Employee Biosafety Room - Lounge
ARCHITECTURAL
CONDITIONING
Ceiling:
Acoustical ceiling tile
0
0
Ceiling Ht:
2740 mm (9'-0")
Dry Bulb Temp Cooling:
25 C (78 F)
0
0
Wall Finish:
Vinyl wall covering
22 C (72 F)
Wainscot:
---
Minimum % Outside Air:
---
Base:
Resilient base
Yes
Floor Finish:
Carpet
Noise Criteria:
NC-40
Slab Depr.:
---
Steam:
---
Notes:
---
Relative Humidity/Cooling:
50%
Relative Humidity/Heating:
30%
Minimum Air Changes/Hr.:
6
SPECIAL EQUIPMENT
Room Pressure:
Negative
22w/m2 (2 w/sf)
AC Load-Equipment:
---
2
AC Load Lighting:
22.5 w/m (2.1 w/sf)
ELECTRICAL LIGHTING
Number of People:
12
---
General:
30FC
Notes:
---
Notes:
1. 600 mm x 1200 mm (2' x 4')
fluorescent
light
PLUMBING AND MEDICAL GAS
fixtures, acrylic prismatic lens,
W/2-=F32T8 lamps, 4100 deg.
Cold Water:
Yes
k, CRI-85 (minimum)
Hot Water:
Yes
Laboratory Air:
---
POWER
Laboratory Vacuum:
---
Sanitary Drain:
---
General:
Reagent Grade Water:
---
strip mold on modular casework)
Medical Air:
---
Emergency:
---
Medical Vacuum:
---
Notes:
---
Oxygen:
---
Notes:
---
ADP:
---
Radio:
---
Telephone:
Yes
Intercom:
Yes
Public Addr:
Yes
Notes:
---
VA DESIGN GUIDE
NUCLEAR MEDICINE SERVICE
5-5