Use lead-lined gypsum wallboard for shielding of X-ray rooms, as shown in Standard Details 13091-1 and
13091-2 for minimum lead protection required. When required by State or Local jurisdictions, Lessor shall
secure the services of a registered physicist to establish the shielding protection required. Refer to
Paragraph 7.5 below.
7.3 INTERIOR DOORS:
Provide solid core wood or hollow metal interior doors. Wood is preferred, except for locations where
metal is required for functional reasons. Follow "Room Finishes, Door and Hardware Schedule" in
Schedule C for sizes and types of doors.
Doors shall be of flush design and shall be in accordance with VA Master Construction Specification 08110
or 08210. Provide metal door frames for wood and metal doors. Wood doors shall comply with National
Wood Window and Door Association (NWWDA) I.S.1. Metal doors and frames shall comply with Steel
Door Institute (SDI)/ ANSI A250.8. Fire rated doors and frames shall comply with NFPA 80.
All corridor-to-corridor doors shall have 100 sq. in. glass vision panels and shall swing in opposite
directions from each other. Doors in fire partitions and smoke barriers shall have fire rated glazing vision
panels and be held open with electromagnetic holders, except doors which should remain closed for
functional reasons.
Do not use wood labeled fire doors in areas where they may be subjected to heavy traffic or hard use,
such as by carts, mobile equipment, etc., nor for pairs of opposite-swinging doors. In these locations, use
hollow metal labeled doors.
//Interior Stairway Doors: Provide interior stairway doors with passage latch sets having inside and outside
door handles free at all times. Exceptions are where stairway doors are required to be locked to prevent
entrance into and elopement from functional departments or areas. Locking shall comply with NFPA 101.//
7.3.1
AUTOMATIC DOORS:
Automatic doors and operators shall be in accordance with VA Master Construction Specification 08721 or
08725. Design automatic doors to operate manually in event of power failure. Equip controls with safety
devices for pedestrian protection. Provide door operator controls and equipment that are easily accessible
for maintenance. Design automatic doors to open from both sides.
Automatic doors are required at the following locations:
//Swinging doors with remote push plate operation:
Main entrance doors to and from Surgery Suite
Entrance Doors to Minor Operating Rooms, and Observation and Treatment Rooms
Recovery Room doors into corridors
[__________}//
//Sliding Doors with //remote push plate// //carpet// controls:
[________________________]//
Finish and color of automatic doors shall match remainder of building. If the sliding doors are to be utilized
and accepted as required exits, the doors shall be designed to open manually in the event of a power
failure in accordance with NFPA 101.