JULY 2005
SOLICITATION FOR OFFERS
OUTPATIENT CLINIC
SFO NO. V101-183R-xxx-xxx-xx
[INSERT LOCATION OF FACILITY]
A.
AREA & EQUIP.
VOLUME
PRESSURE
scfm
psi
6.
Threaded valve for shellblaster or sandblaster
10
140
100
7.
Threaded valve for microblaster
3
140
100
B.
NUMBER OF OUTLETS, REQUIRING
PERCENT SIMULTANEOUS
1.
3 and 10 SCFM
a.
1 through 3
100
b.
4 through 6
90
c.
7 through 9
80
d.
10 through 12
70
e.
13 through 16
60
f.
17 and over
50
2.
0.25 SCFM
a.
1 through 5
40
b.
6 through 10
30
c.
11 through 19
20
d.
20 and over
10
//
Editing Note: Include following paragraph if
engineering shops or prosthetics labs are in project.
6.6.15 //SHOP COMPRESSED AIR SYSTEMS// //RESERVED//:
//Shop air systems shall not be cross connected or used for instrument air (HVAC control air). Provide
simplex air compressor to serve equipment and a minimum of one outlet on each wall in shop areas.
Interior outlets shall be no farther apart than 25 feet.//
6.6.16 //WATER TREATMENT SYSTEMS// // RESERVED//:
//When required based on water analysis, provide water softening and/or de-alkalizing systems for
building.
Editing Note: Include water softening system if total
hardness exceeds criteria listed below.
6.6.16.1 WATER SOFTENING SYSTEM:
6.6.16.1.1 Softeners
Design vertical, pressure type, sodium cycle water softeners to comply with the following and VA Master
Construction Specification 15455. Regeneration shall occur no more than once per day. Provide bypass.
Provide softening equipment for entire outpatient clinic when total hardness exceeds 170 mg/L (ppm) as
CaCO3. Blend equipment effluent to a hardness of approximately 50 mg/L.
Part I: Basic Solicitation Requirements Page 114 of 169
Lessor __________ Gov't. __________
__________ of __________ Pages