JULY 2005
Design Standards
Radiology General Purpose Room
Security/Duress:
Yes
ARCHITECTURAL
VTEL:
--
Coordinate with SFO; refer to Template SFO
VA Satellite TV:
--
Notes:
--
Schedule C.
Ceiling:
AT with X-Ray Support
Ceiling Height:
2895 mm (9'-6")
CONDITIONING
Wall Finish:
Painted GWB
Coordinate with SFO; refer to Template SFO
Wainscot:
--
Section 6.5.
Base:
Resilient Base
23C (75F)
Dry Bulb Temp Cooling:
Floor Finish:
26C (78F)
Slab Depression:
--
Minimum % Outside Air:
15%
Sound Protection:
--
--
Notes:
Lead lined partitions
Noise Criteria:
NC-40
and door
Steam:
--
LIGHTING
Relative Humidity/Cooling:
50%
Relative Humidity/Heating:
30%
Coordinate with SFO; refer to Template SFO
Minimum Air Changes/Hr.:
6
Section 6.7, 6.7.1, 6.7.5.
Room Pressure:
0
General:
10 FC Control Console
AC Load-Equipment:
5 W/SF (Note 1)
Alcove
AC Load-Lighting:
2 W/SF
0-50 FC Radiology
Number of People:
2
Room-Fluorescent
--
0-10 FC Radiology
Notes:
1. Check with
Room-Incandescent
equipment
Special:
Yes
manufacturer for
Notes:
Incandescent fixtures
shall be dimmable.
Provide dimmer
PLUMBING AND MEDICAL GASES
switches sized per
maximum load.
Coordinate with SFO; refer to Template SFO
Section 6.6 and Schedule B
POWER
Cold Water:
Yes
Coordinate with SFO; refer to Template SFO
Hot Water:
Yes
Section 6.7, 6.7.1, 6.7.3, 6.7.4 and Schedule B.
Laboratory Air:
--
General:
Yes
Laboratory Vacuum:
--
Emergency:
--
Sanitary Drain:
Yes
Notes:
--
Reagent grade Water:
--
Medical Air:
--
COMMUNICATION/SPECIAL SYSTEMS
Medical Vacuum:
--
Oxygen:
--
Coordinate with SFO; refer to Template SFO
Notes:
--
Sections 6.7.8, 6.7.9, and Schedule B.
Data:
Yes
Telephone:
Yes
Intercom:
--
Nurse Call:
--
Public Address:
--
Radio/Entertainment: --
MATV:
--
CCTV:
--
MID:
--
VA DESIGN GUIDE
APPENDIX B
LEASE BASED OUTPATIENT CLINICS
2-15.3