JULY 2005
Design Standards
Proctoscopy/ Sigmoidoscopy Room
COMMUNICATION/SPECIAL SYSTEMS
ARCHITECTURAL
Coordinate with SFO; refer to Template SFO
Coordinate with SFO; refer to Template SFO
Sections 6.7.8, 6.7.9, and Schedule B.
Section 7, and Schedule C.
Data:
Yes
Ceiling:
GWB Lay-in Panels
Telephone:
Yes
AT in Toilet Room
Intercom:
--
Ceiling Height:
2740 mm (9'-0")
Nurse Call:
Yes
Wall Finish:
Painted GWB
Public Address:
--
Wainscot:
--
Radio/Entertainment: --
Base:
RSF, Integral Base; CT
MATV:
--
In Toilet Room
CCTV:
--
Floor Finish:
RSF; CT in Toilet Room
MID:
--
Slab Depression:
--
Security/Duress:
--
Sound Protection:
STC 40
VTEL:
--
Notes:
--
VA Satellite TV:
--
Notes:
--
LIGHTING
Coordinate with SFO; refer to Template SFO
CONDITIONING
Section 6.7, 6.7.1, 6.7.5.
Coordinate with SFO; refer to Template SFO
General:
Proctoscopy/
Section 6.5.
Sigmoidoscopy 100 FC
Toilet 30 FC
22C (73F)
Dry Bulb Temp Cooling:
Special:
Yes
26C (78F)
Notes:
1. Portable examining
Minimum % Outside Air:
100%
light.
Yes
2. Emergency critical
Noise Criteria:
NC-40
power source 50% of
Steam:
--
lighting.
Relative Humidity/Cooling:
50%
3. 2' X 4' fluorescent
Relative Humidity/Heating:
30%
Minimum Air Changes/Hr.:
6
with acrylic prismatic
Room Pressure:
Negative
lens.
AC Load-Equipment:
5 W/SF
AC Load-Lighting:
2 W/SF
POWER
Number of People:
4
--
Coordinate with SFO; refer to Template SFO
Notes:
--
Section 6.7, 6.7.1, 6.7.3, 6.7.4 and Schedule B.
General:
Yes
PLUMBING AND MEDICAL GASES
Emergency:
Yes
Coordinate with SFO; refer to Template SFO
Notes:
1. Special wiring device for
Section 6.6 and Schedule B
laser unit. Coordinate
Cold Water:
Yes
with manufacturer.
Hot Water:
Yes
2. Floor mounted junction
Laboratory Air:
--
box for examine
Laboratory Vacuum:
--
treatment table.
Sanitary Drain:
Yes
Reagent grade Water:
--
Medical Air:
Yes
Medical Vacuum:
Yes
Oxygen:
--
Notes:
--
VA DESIGN GUIDE
APPENDIX B
LEASE BASED OUTPATIENT CLINICS
2-14.3