September 30, 1995
Design Standards
Acid Storage Room
ARCHITECTURAL
Floor Area
9 m (97 ft)
Wall Finish
cmu
Ceiling
gwb
Base
rb
Ceiling Height
2700 mm (9 ft)
Floor Finish
c (treated)
RFI Shielding
-
Slab Depression
-
Soundproofing
-
Floor Load
-
Lighting
ELECTRICAL
Power
General
550 lx (50 fc)
General
-
Special
-
Special
-
Emergency
-
Emergency
-
Telephone
-
ADP
-
HEATING, VENTILATING AND AIR CONDITIONING
AC Load Lights
140 W
Dry Bulb Temp Cooling
26C (78F)
AC Load Equipment
-
22C (72F)
Number of People
-
Relative Humidity - Cooling
50%
Noise Criteria
NC-45
Relative Humidity - Heating
30%
Room Pressure
negative
Minimum % Outside Air
100
Min Air Changes per Hour 4
yes
Steam
-
Special Exhaust
yes
Provide dedicated exhaust system for room, with acid resistant epoxy coating on exhaust fan.
Ductwork to be fiberglass reinforced polyester resin self-extinguishing material, or galvanized plastic coated (PVC)
acid-resistant material.
PLUMBING AND LABORATORY GASES
Sanitary Drain
-
Cold Water
-
Acid Waste
-
Hot Water
-
Other
-
Reagent Grade Water
-
Fuel Gas
-
Laboratory Air
-
-
Laboratory Vacuum
-
Guide Plate 6-5
VA Design Guide -- Research Laboratory