September 30, 1995
Design Standards
Glassware Washing and Sterilization Room
ARCHITECTURAL
Floor Area
38 m (406 ft)
Wall Finish
cmu/sc
Ceiling
at (sp)
Base
erf
Ceiling Height
2700 mm (9 ft)
Floor Finish
erf
RFI Shielding
-
Slab Depression
-
Soundproofing
-
Floor Load
-
SPECIAL EQUIPMENT
HW517 Glassware washing machine
VS260 Sterilizer
DW 911 Still
K3010 Ice Machine
Lighting
ELECTRICAL
Power
General
750 lx (70 fc)
General
-
Special
1100 lx (100 fc) task
Special
-
Louvered deep cell parabolic fixtures, T-8 lamps
Emergency
-
Telephone
yes
ADP
yes
HEATING, VENTILATING AND AIR CONDITIONING
AC Load Lights
1120 W
Dry Bulb Temp Cooling
27 C (80F)
AC Load Equipment
65 W/m (6.0 W/ft)
21 C (70F)
Number of People
2 to 3
Relative Humidity - Cooling
60%
Noise Criteria
NC-40
Relative Humidity - Heating
-%
Room Pressure
negative
Minimum % Outside Air
100
Min Air Changes per Hour 15
100% Exhaust Air
yes
Steam
275 kPa (40-60 psig)
Special Exhaust
yes
See PG-08-6 for steam, heat gain, & exhaust capacities. See PG-08-4 Volume 3 Section II for Type `B' hood
details.
Provide a dedicated exhaust system with liquid-tight stainless steel ductwork.
Limit temp rise in service area to 8.3C (15F) above disassembling area.
PLUMBING AND LABORATORY GASES
Sanitary Drain
yes
Cold Water
yes
Acid Waste
yes
Hot Water
yes
Other
-
Reagent Grade Water
yes
Fuel Gas
-
Laboratory Air
yes
-
Laboratory Vacuum
-
Guide Plate 6-2
VA Design Guide -- Research Laboratory