September 30, 1995
Design Standards
Cold Procedure Room
ARCHITECTURAL
Floor Area
7.5 m (81 ft)*
Wall Finish
prefab
Ceiling
prefab
Base
-
Ceiling Height
-
Floor Finish
prefab
RFI Shielding
-
Slab Depression
yes
Soundproofing
-
Floor Load
-
*Prefabricated, see PG-08-1 MCS 13062, H-08-3 CS 643-1
Lighting
ELECTRICAL
Power
General
750 lx (70 fc)
General
GFI
Special
-
Special
-
Incandescent fixtures
Emergency
-
Telephone
-
ADP
-
HEATING, VENTILATING AND AIR CONDITIONING
AC Load Lights
-
Dry Bulb Temp Cooling
4C (40F)
AC Load Equipment
-
-
Number of People
-
Relative Humidity - Cooling
-%
Noise Criteria
-
Relative Humidity - Heating
-%
Room Pressure
-
Minimum % Outside Air
-
Min Air Changes per Hour -
-
Steam
-
Special Exhaust
-
Provide minimum 42 m/s (25 cfm) supply and exhaust air.
PLUMBING AND LABORATORY GASES
Sanitary Drain
yes
Cold Water
yes
Acid Waste
-
Hot Water
yes
Other
-
Reagent Grade Water
-
Fuel Gas
-
Laboratory Air
-
-
Laboratory Vacuum
-
Guide Plate 6-1
VA Design Guide -- Research Laboratory