740
Example Service Module: Alteration
743
ALTERATION
743.1
FUNCTIONAL ZONE
To demonstrate the effect of functional zone replanning, it is assumed that
the radiology suite in the opening configuration requires expansion to
nearly twice its original size, from four to seven radiology rooms, including
a special procedures room. To achieve this, the outpatient department is
relocated elsewhere and some offices taken over to supplement the
departmental offices.
The change of use of the offices causes little alteration to service layouts,
but the new radiology rooms require complete alteration of the branch
services in that area.
Figure 740-8 shows the revised layout with proposed service drops in the
area affected by the change.
743.2
SERVICE ZONE
Figures 740-9, 10, and 11 show the revised layouts for the three services.
In each case, the main distribution remains unchanged.
743.2.1
Main Distribution
The HVC supply and general exhaust/return main ducts are all permanent
installations sized to handle up to the maximum air flow of 24,000 cfm and
the alteration of functions in this example does not significantly change the
cfm requirement from before. The slight increase in toilet exhaust
requirement can be handled by the original duct.
The electrical and plumbing main distribution remain constant with some
circuit variation in the wireways, and the generally oversized plumbing
mains are capable of handling the increase in load.
743.2.2
Branch Distribution
The branch distribution in the changed area requires either extension or
replacement.
3 - 159