510
Generalized Needs and Requirements: Hospital Requirements
513.8.2
Attachment Requirements
The following items may be attached to a partition, a ceiling or to the
structural slab:
Items
Example Loading
1. Moving radiographic tube hanger
750#
2. Moving laundry bag conveyor
400#
3. Moving patient hoist
300#
4. Lead lined 4'-0"
1,200#
5. Image Intensifier
185#
6. Lead shielding
32 psf
185#
8. 10-gal. distilled water carboy
630#
4,000#
10. Surgical gas column
350#
11. Orthopedic hook
300#
12. Surgical light
3,600#
13. X-ray shielding
32 psf max.
14. Grab bars
200#
2 - 42