EQUIPMENT GUIDE LIST - CHAPTER 276
07-02
RADIOLOGY SERVICE
SYMBOL
QNTY
ACQ/INS
DESCRIPTION
SPEC
REFERENCE
DETAIL
PROCESSOR, FILM, AUTOMATED (TYPE OF FILM PROCESSOR-TOP
1
VC
OR END FILM DISCHARGE TO BE DETERMINED ON PROJECT BASIS)
FLOOR DRAIN, NEAR FILM PROCESSING UNITS (PLUMBING DESIGN
1
CC
CRITERIA AND INSTRUCTIONS)
TANK, REPLENISHER, 95 L (25 GAL.) CAPACITY AND CURBING, 2 FOR
1
VC
EACH PROCESSOR
FLOOR DRAIN, NEAR REPLENISHER TANK UNITS (PLUMBING DESIGN
1
CC
CRITERIA & INSTRUCTIONS)
HOSE BIBB, COMBINATION FAUCET, WALL MOUNTED, CONCEALED
P-802
1
CC
SUPPLY PIPES
15450
CONNECTIONS, PLUMBING, ELECTRICAL OR MECHANICAL AS
AR
CC
REQUIRED
NOTE: PROVIDE PIPING CONNECTION FROM PROCESSORS TO
SILVER RECOVERY SYSTEM, IF REQUIRED.
CONTROL AREA:
AR
CC
WINDOW, LEAD GLASS, MINIMUM 457 mm X 610 mm (18" X 24")
13091
CONSOLE, CONTROL, X-RAY, FOR AUTOMATED CHEST UNIT
1
VC
(CAPACITY OF GENERATOR TO BE DETERMINED ON PROJECT
AR
CC
INCANDESCENT, DIMMING SYSTEM
16510
ILLUMINATOR, X-RAY, 120 VOLT, 20 AMP, WALL MOUNTED, APPROX.,
1
VV
508 mm X 1499 mm (20" X 59"), 4 IN 1
AR
CC
LIGHT, WARNING (DO NOT ENTER) OVER DOOR
GENERAL PURPOSE ROOMS:
1
VC
RADIOGRAPHIC UNIT - CONSISTS OF THE FOLLOWING
1
VC
STARTER, TUBE, HIGH SPEED
1
VC
MODULE, POWER
1
VC
1
VC
TABLE, RADIOGRAPHIC, FLAT BUCKY
-OR-
1
VC
TABLE, TILT, 90 DEGREE VERTICAL, 15 DEGREE TRENDELENBURG
TABLE, FLAT, MODIFIED WITH TRAY FOR MULTI CASSETTES FOR
BODY SECTIONAL TECHNIQUE (PROVIDE ONLY WHEN APPROVED
1
VC
FOR A SPECIFIC PROJECT)
1
VC
TUBE CARRIAGE, CEILING MOUNTED
Page 30