Attachment No. 3 SECONDARY DISTRIBUTION INTERFACE
See paragraph 5.5
Notes:
1. Provide 15% (minimum) pump flow by use of a 3 way control valve.
2. Alternately provide a 2 way control valve for CC-3 and a 2 way automatic
bypass valve at CC-3 to provide for an automatic bypass of chilled water
when the coil control valve begins to close. The automatic bypass valve and
line shall be sized to handle 15% (minimum) pump flow.