(f) Space temperature indication:
(1) Recovery room
(2) Each intensive care unit
(3) Cardiac procedures room
(g) Pressure indication with high/low alarm:
(h) Chilled water plant:
(1) Chilled water supply and return temperatures and flow rates
(2) Condenser water supply and return temperatures and flow rates
(1) Heating water supply temperatures and flow rate
(2) Glycol/water system, supply and return
2.14.2.8 The following programs shall be provided as applicable:
(a) Time initiated programs
(b) Optimum start/stop
(c) Enthalpy optimization/economizers
(d) Duty cycling (Do not specify for VAV systems)
(e) Chilled water plant optimization
(f) Automatic restart of equipment sequence after power outage and upon
resumption of commercial power service, and upon application of
emergency power
(g) Power demand limiting
(h) Preventative maintenance instruction
(i) Fire emergency
(j) Calculating of air flows, water flows, tonnage, BTUs, W, kW, Kg/s,
Cu M/Min, L/Min, (BTU, Tons, Lb./Hr., CFM, GPM), etc.
(k) Optimization control of hot deck and cold deck temperatures; air
quantity control in VAV systems
(l) Optimization of lighting use
(m) Computer Diagnostic and Testing Programs: To test all programs and
report malfunctions down to specific items or circuits