curtain tracks are to be surface mounted and should be shown on
the 1:100 (1/8") reflected ceiling plans.
18.4
Except for specific areas requiring special treatment, all
suspended acoustic tile ceilings shall be 600 by 1200 mm (2 x 4)
lay-in panels in a standard 25 mm (1") grid.
CEILING HEIGHTS: Minimum clear ceiling heights from finished floor to
19.
finished ceiling shall be 2.4 m (8'0") except for areas listed below.
a.
Dining Room
(9'-6")
2.9
m
b.
Rehab Medicine Areas
(9'-6")
2.9
m
c.
Recreation room
(9'-0")
2.7
m
d.
Lounge
(9'-0")
2.7
m
e.
Dietetics: Serving unit, tray
(9'-0")
2.7
m
make-up, food processing & preparation
f.
Canteen
2.7 m (9'-0")
g.
Bedrooms with Ceiling-hung TV's
2000 mm (6'8")
Height as required for below TV
20.
PARAPET WALLS, ROOF STRUCTURE, AND WALKWAYS:
20.1
Masonry parapet walls are potential sources of water penetration,
unequal thermal expansion, additional structural loads, and
increased costs. Therefore, do not use such walls for any
building unless specifically permitted by the Project Manager.
Proposed parapet walls must be justified by aesthetic, functional
or economic considerations. Where permitted, design and reinforce
them to assure stability and water tightness when subjected to
lateral or thermal forces.
20.2
Make roof structures, such as penthouses and architectural screens
enclosing or concealing roof-mounted mechanical equipment,
compatible in appearance and with the material, texture, color,
and shape of the building. Where it is necessary to expose
roof-mounted mechanical equipment, minimize its appearance by
location, low silhouette, and color.
20.3
Provide roof walkways of prefabricated asphalt planks with nonslip
surfaces on access routes over roofs to mechanical equipment
requiring recurrent maintenance. Where necessary for safety of
maintenance workers, provide ladders, stairs and/or platforms.
Show their location and provide details on architectural drawings.
20.4
In attic spaces to have batt or loose floor insulation, provide
walkways for access to mechanical and electrical equipment. Show
the location and details of attic walkways on architectural
drawings.
20.5
Whenever mechanical equipment requiring periodic maintenance is
installed on a roof more than 6 m (20 feet) above the ground,
provide guardrails or fences between the roof edge and any
equipment or walkways less than 3 m (10 feet) from the edge.
Design the guardrails 1050 mm (42 inches) high and in accordance
with OSHA requirements for standard guardrails.
21.
LOW SLOPE ROOF SYSTEMS:
14