Draft 7-6-95
Design Standards
Blood Specimen Collection Room
ARCHITECTURAL
CONDITIONING
Ceiling:
GWB
Ceiling Ht:
2400 mm (8'-0")
Dry Bulb Temp Cooling:
25C (78F)
Wall Finish:
GWB
22C (72F)
Wainscot:
--
Minimum % Outside Air:
15%
Base:
4" Resilient Base
Noise Criteria:
NC-40
Floor Finish:
Steam:
--
Slab Depr:
--
Relative Humidity/Cooling:
50%
Notes:
Relative Humidity/Heating:
30%
Minimum Air Changes/Hr.:
4
SPECIAL EQUIPMENT
Room Pressure:
0
AC Load-Equipment:
3.0 W/SF
None
AC Load-Lighting:
1.7 W/SF
LIGHTING
Number of People:
2
--
General:
1080 W
Notes:
--
Special:
--
Notes:
PLUMBING AND MEDICAL GASES
POWER
Cold Water:
Yes
Hot Water:
Yes
General:
1080 W
Laboratory Air:
--
Emergency:
--
Laboratory Vacuum:
--
Notes:
--
Sanitary Drain:
Yes
COMMUNICATION
Reagent Grade Water:
--
Medical Air:
--
ADP:
--
Medical Vacuum:
--
Radio:
--
Oxygen:
--
Telephone:
Yes
Notes:
Intercom:
--
Pub. Addr:
--
Notes:
VA Design Guide
Community Based Outpatient Clinic
PAGE 5 -3