Draft 7-6-95
Design Standards
Nurse Station
ARCHITECTURAL
CONDITIONING
Ceiling:
Ceiling Ht:
2400 mm (8'-0")
Dry Bulb Temp Cooling:
25C (78F)
Wall Finish:
GWB
22C (72F)
Wainscot:
--
Minimum % Outside Air:
15%
Base:
4" Resilient Base
--
Floor Finish:
Carpet
Noise Criteria:
NC-40
Slab Depr:
--
Steam:
--
Notes:
Relative Humidity/Cooling:
50%
Relative Humidity/Heating:
30%
SPECIAL EQUIPMENT
Minimum Air Changes/Hr.:
4
Room Pressure:
0
None
AC Load-Equipment:
3.4w/sf
LIGHTING
AC Load-Lighting:
2.5w/sf
Number of People:
2
General:
70FC - 3.5W/SF
--
Special:
--
Notes:
--
Notes:
1. Downspots over counter
POWER
PLUMBING AND MEDICAL GASES
General:
--
Cold Water:
Yes
Emergency:
--
Hot Water:
Yes
Notes:
--
Laboratory Air:
--
Laboratory Vacuum:
--
COMMUNICATION
Sanitary Drain:
Yes
Reagent Grade Water:
--
ADP:
Yes
Medical Air:
--
Radio:
--
Medical Vacuum:
--
Telephone:
Yes
Oxygen:
--
Intercom:
Yes
Other:
AAP
Pub. Addr:
Yes
Notes:
Code One:
Yes
Paging:
Yes
Notes:
VA Design Guide
PAGE 5 -2
Community Based Outpatient Clinic