Draft 7-6-95
Design Standards
Medical Records & X-ray Storage
ARCHITECTURAL
CONDITIONING
Ceiling:
GWB
Ceiling Ht:
2400 mm (8'-0")
Dry Bulb Temp Cooling:
25C (78F)
Wall Finish:
GWB
22C (72F)
Wainscot:
--
Minimum % Outside Air:
25%
Base:
4" Resilient Base
Noise Criteria:
NC-40
Floor Finish:
VCT
Steam:
--
Slab Depr:
--
Relative Humidity/Cooling:
50%
Notes: 1. Full height partitions around
Relative Humidity/Heating:
30%
perimeter.
Minimum Air Changes/Hr.:
4
Room Pressure:
0
SPECIAL EQUIPMENT
AC Load-Equipment:
2.1W/SF
AC Load-Lighting:
2.1W/SF
None
Number of People:
1
LIGHTING
--
Notes:
--
General:
50FC - 2.5 W/SF
Special:
--
PLUMBING AND MEDICAL GASES
Notes:
Cold Water:
--
POWER
Hot Water:
--
Laboratory Air:
--
General:
--
Laboratory Vacuum:
--
Emergency:
--
Sanitary Drain:
--
Notes:
--
Reagent Grade Water:
--
COMMUNICATION
Medical Air:
--
Medical Vacuum:
--
ADP:
--
Oxygen:
--
Radio:
--
Notes:
Telephone:
--
Intercom:
--
Pub. Addr:
--
Notes:
VA Design Guide
Community Based Outpatient Clinic
PAGE 4 -3