Draft 7-6-95
Design Standards
Workroom
ARCHITECTURAL
CONDITIONING
Ceiling:
Ceiling Ht:
2400 mm (8'-0")
Dry Bulb Temp Cooling:
25C (78F)
Wall Finish:
22C (72F)
GWB
Minimum % Outside Air:
15%
Wainscot:
--
Noise Criteria:
NC-40
Base:
4" Resilient Base
Steam:
--
Floor Finish:
Carpet
Relative Humidity/Cooling:
50%
Slab Depr:
--
Relative Humidity/Heating:
30%
Notes:
Minimum Air Changes/Hr.:
4
Room Pressure:
0
AC Load-Equipment:
4.6W/SF
SPECIAL EQUIPMENT
AC Load-Lighting:
2.6W/SF
Number of People:
2
--
None
Notes:
--
LIGHTING
PLUMBING AND MEDICAL GASES
General:
70FC - 3.5W/SF
Special:
--
Cold Water:
--
Hot Water:
--
Notes:
Laboratory Air:
--
POWER
Laboratory Vacuum:
--
Sanitary Drain:
--
General:
1200W
Reagent Grade Water:
--
Emergency:
--
Medical Air:
--
Notes:
--
Medical Vacuum:
--
COMMUNICATION
Oxygen:
--
Notes:
ADP:
Yes
Radio:
--
Telephone:
Yes
Intercom:
--
Pub. Addr:
--
Notes:
VA Design Guide
Community Based Outpatient Clinic
PAGE 4 -3