FINAL DRAFT 10-31-95
REVISED January 1997
Design Standards
ARCHITECTURAL
CONDITIONING
Ceiling:
Ceiling Ht:
2700 mm (9'-0")
Dry Bulb Temp Cooling:
25C (78F)
Wall Finish:
Vinyl fabric wall covering
22C (72F)
Wainscot:
--
Minimum % Outside Air:
15
Base:
Resilient base
--
Floor Finish: Carpet
Noise Criteria:
NC-40
Slab Depr:
--
Steam:
--
Notes:
1. 900 mm (3'-0") wide door.
Relative Humidity/Cooling:
50%
Relative Humidity/Heating:
30%
SPECIAL EQUIPMENT
Minimum Air Changes/Hr.:
4
Room Pressure:
0
None
2
AC Load Lighting:
30 W/m (2.8 W/sf)
65 W/m 2 (6 W/sf)
AC Load-Equipment:
LIGHTING
Number of People:
6
General:
50 FC
--
Special:
--
Notes:
Notes:
1. Lighting control by area;
switches at room entries.
PLUMBING AND MEDICAL GASES
2. 600 mm x 1200 mm (2'x4')
Cold Water:
--
Hot Water:
--
fixture, 8-cell parabolic
Laboratory Air:
--
louver, W/2-F32T8 lamps,
Sanitary Drain:
--
3500K, CRI=75 (Minimum)
Reagent Grade Water:
--
Medical Air:
--
POWER
Medical Vacuum:
--
General:
Oxygen:
--
Emergency:
--
Notes:
Notes:
COMMUNICATION
ADP:
Yes
Radio:
--
Telephone:
Yes
Intercom:
--
Pub. Addr:
--
Notes:
VA DESIGN GUIDE
AMBULATORY CARE (Hospital Based)
PAGE 6-4