FINAL DRAFT 10-31-95
REVISED January 1997
Design Standards
Women's Health GYN Examination Room
ARCHITECTURAL
CONDITIONING
Ceiling:
Gypsum wallboard in toilet; lay-
in panels in exam room
Dry Bulb Temp Cooling:
24C (76F)
Ceiling Ht
2700 mm (9'-0")
25C (78F)
Wall Finish:
Paint (Ceramic tile in toilet rm)
Minimum % Outside Air:
15%
Wainscot:
--
Toilet room only
Base:
Resilient base
Noise Criteria:
NC-35
Steam:
--
Slab Depr:
--
Relative Humidity/Cooling:
50%
Notes:
1. Provide STC 40 for partitions
Relative Humidity/Heating:
30%
and door
Minimum Air Changes/Hr.:
4
2. 900 mm (3'-0") wide door
Room Pressure:
Exam room is 0
Toilet is negative
15 W/m 2(1.4 W/sf)
SPECIAL EQUIPMENT
AC Load Lighting:
AC Load-Equipment:
None
Number of People:
3
--
LIGHTING
Notes:
General:
Exam Room: 50 FC
Toilet: 30 FC
Special:
--
PLUMBING AND MEDICAL GASES
Notes:
1. 600 mm x 1200 mm (2'x4')
Cold Water:
Yes
fixture, acrylic prismatic lens,
Hot Water:
Yes
W/3-F32T8 lamps, 4100K,
Laboratory Air:
--
Laboratory Vacuum:
--
CRI=85 (Minimum)
Sanitary Drain:
--
Reagent Grade Water:
--
POWER
Medical Air:
--
General:
Medical Vacuum:
--
Emergency:
--
Oxygen:
--
Notes:
Notes:
COMMUNICATION
ADP:
Yes
Radio:
--
Telephone:
Yes
Intercom:
--
Pub. Addr:
--
Notes:
VA DESIGN GUIDE
AMBULATORY CARE (Hospital Based)
PAGE 6-3