H. NOTES:
1. Identify the dedicated and thermostatically controlled HVAC sub-systems for
spaces, such as, mechanical equipment rooms, electrical equipment rooms, telephone
equipment rooms, computer rooms, elevator machine rooms, emergency generator
rooms, vestibules, exterior stairs etc.;
2.
Calculate in watts per gross square meter (BTUs per gross square foot) per year;
3. Show interface between existing and new lines and available spare capacities of
existing utilities; and
4. Provide single line schematic and control diagrams and a written sequence of
operation describing the control architecture (number of panels, interface, if any, with
central Engineering Control Center strategy, safety features, alarms, logic, etc. Provide
direct digital control (DDC) systems.