26 February 1993
Procedural Laboratory (Chemical/Radioisotope Suite)
Design Standards
ARCHITECTURAL
HEATING, VENTILATING AND AIR CONDITIONING
Floor Area
200 NSF
Wall Finish
CMU (SC)
AC Load Lights
4.0 W/SF
Ceiling
PCP
Wainscot
-
AC Load Equipment
5.2 W/SF
Ceiling Height
9'-0"
Base
ERF
Number of People
3
Slab Depression
-
Floor Finish
ERF
Noise Criteria
NC-40
Notes:
Lead Lining
-
Room Pressure
NEGATIVE
Dry Bulb Temp Cooling (F)
78
72
Minimum Air Changes per Hour
15 (SA)
Minimum % Outside Air
100
YES
SPECIAL EQUIPMENT
YES*
H3-72 RADIOISOTOPE HOOD
Steam
-
REFRIGERATOR
Relative Humidity - Cooling
50 %
Relative Humidity - Heating
30 %
Notes:
ELECTRICAL
*H3: 1375 CFM, 0.375" PD; SEE H-08-4 SD 673.5
Lighting
Power
General
70 FC, 3.5 W/SF*
General
1080 W
Special
-
Special
**
Emergency
50% GEN FLUOR
Emergency
**
Notes:
*COLOR CORRECTED FLUOR LAMPS
PLUMBING AND MEDICAL GASES
Sanitary Drain
YES
Cold Water
YES
**H3: 600 W; REFRIGERATOR: 1200 W; EMERGENCY CIRCUIT
Acid Waste
YES
Hot Water
YES
Silver Recovery
-
Reagent Water
-
Medical Air
-
Laboratory Air
YES
Medical Vacuum -
Laboratory Vacuum YES
Oxygen
-
Fuel Gas
YES
Telephone
WALL MTD
ADP
EMPTY CONDUIT
Nitrous Oxide
-
Anesthesia Evac
-
Intercom
PART OF TELEPHONE
Radio
-
Notes:
Public Address
-
Other
-
H3: LAB AIR, LAB VACUUM, FUEL GAS, COLD WATER, ACID WASTE
Notes:
VA Design Guide -- Veterinary Medical Unit
Guide Plate 7-1