26 February 1993
Surgical Work Room and Supply
Design Standards
HEATING, VENTILATING AND AIR CONDITIONING
ARCHITECTURAL
Floor Area
145 NSF
Wall Finish
CMU (SC)
AC Load Lights
2.8 W/SF
Ceiling
PCP
Wainscot
-
AC Load Equipment
1.9 W/SF*
Ceiling Height
9'-0"
Base
ERF
Number of People
2
Slab Depression
-
Floor Finish
ERF
Noise Criteria
NC-40
Notes:
Lead Lining
-
Room Pressure
POSITIVE
Dry Bulb Temp Cooling (F)
78
72
Minimum Air Changes per Hour
4 (SA)
Minimum % Outside Air
100
YES
SPECIAL EQUIPMENT
YES*
VS-201 STERILIZER
Steam
YES*
Relative Humidity - Cooling
50 %
Relative Humidity - Heating
30 %
Notes:
ELECTRICAL
*VS-201: SEE H-08-6 FOR STEAM, HEAT GAIN AND INTEGRAL
CANOPY HOOD
Lighting
Power
General
70 FC, 3.5 W/SF
General
540 W
Special
-
Special
*
Emergency
50% GEN FLUOR
Emergency
-
Notes:
PLUMBING AND MEDICAL GASES
Sanitary Drain
YES
Cold Water
YES
*VS-201: PUMP-12 A, 480 V; CONTROLS-25 A, 120 V;
Acid Waste
-
Hot Water
YES
SENSOR CONTROL-1 A, 120 V
Silver Recovery
-
Reagent Water
YES
Medical Air
-
Laboratory Air
-
Medical Vacuum
-
Laboratory Vacuum
-
Oxygen
-
Fuel Gas
-
Telephone
-
ADP
-
Nitrous Oxide
-
Anesthesia Evac
-
Intercom
-
Radio
-
Notes:
Public Address
-
Other
-
Notes:
VA Design Guide -- Veterinary Medical Unit
Guide Plate 6-4