26 February 1993
Cage Wash Room
Design Standards
ARCHITECTURAL
HEATING, VENTILATING AND AIR CONDITIONING
Floor Area
615 NSF
Wall Finish
CMU (SC)
AC Load Lights
1.3 W/SF--1.2 W/SF
Ceiling
PCP
Wainscot
-
AC Load Equipment
4.7 W/SF--8.4 W/SF
Ceiling Height
9'-6"
Base
ERF
Number of People
3--2
Slab Depression
12"-14"*
Floor Finish
ERF
Noise Criteria
NC-40
Notes:
Lead Lining
-
Room Pressure
NEGATIVE--POSITIVE
*SEE H-08-3 CS 5-2
Dry Bulb Temp Cooling (F)
78
72
Minimum Air Changes per Hour
15 (SA)
Minimum % Outside Air
100
YES
SPECIAL EQUIPMENT
Special Exhaust
YES*
HW-509 BOTTLE WASHER/FILLER
Steam
YES*
HW-546 CASE AND RACK WASHER
Relative Humidity - Cooling
50 %
VS-261 STERILIZER
Relative Humidity - Heating
30 %
Notes:
ELECTRICAL
(DIRTY--CLEAN) AREA VALUES ARE SHOWN SEPARATELY
*HW-546, HW-509, VS-261: SEE H-08-6 FOR STEAM, HEAT GAIN
Lighting
Power
AND EXH CAPACITIES
General
30 FC, 1.5 W/SF
General
900 W
USE STAINLESS STEEL EXHAUST DUCTWORK WHERE EXPOSED
Special
-
Special
*
Emergency
-
Emergency
-
Notes:
PLUMBING AND MEDICAL GASES
Sanitary Drain
YES
Cold Water
YES
*HW-546: 30 A, 250 V, 3 PHASE
Acid Waste
-
Hot Water
YES
HW-509: 10 A, 120 V, 1 PHASE
Silver Recovery
-
Reagent Water
-
VS-261: 25 A, 120 V
Medical Air
-
Laboratory Air
-
Medical Vacuum
-
Laboratory Vacuum
-
Oxygen
-
Fuel Gas
-
Telephone
-
ADP
-
Nitrous Oxide
-
Anesthesia Evac
-
Intercom
-
Radio
-
Notes:
Public Address
-
Other
-
Notes:
VA Design Guide -- Veterinary Medical Unit
Guide Plate 5-12