26 February 1993
Necropsy
Design Standards
ARCHITECTURAL
HEATING, VENTILATING AND AIR CONDITIONING
Floor Area
120 NSF
Wall Finish
CMU (SC)
AC Load Lights
5.0 W/SF
Ceiling
PCP
Wainscot
-
AC Load Equipment
17.0 W/SF*
Ceiling Height
9'-0"
Base
ERF
Number of People
3
Slab Depression
-
Floor Finish
ERF
Noise Criteria
NC-40
Notes:
Lead Lining
-
Room Pressure
NEGATIVE
Dry Bulb Temp Cooling (F)
76
76
Minimum Air Changes per Hour
15 (SA)
Minimum % Outside Air
100
YES
SPECIAL EQUIPMENT
YES**
HW-800 NECROPSY TABLE
Steam
-
TRIMMING TABLE
Relative Humidity - Cooling
60 %
Relative Humidity - Heating
30 %
Notes:
ELECTRICAL
*EXAM LIGHT INCLUDED AS EQUIPMENT LOAD
**SEE HVAC DESIGN MANUAL "AUTOPSY" FOR EXH REQUIREMENTS
Lighting
Power
General
70 FC, 3.5 W/SF*
General
1080 W
Special
**
Special
***
Emergency
33% GEN FLUOR
Emergency
-
Notes:
*FLUOR LAMPS COLOR CORRECTED
PLUMBING AND MEDICAL GASES
**(1) SURGICAL LIGHT, 2 HEADS
Sanitary Drain
YES
Cold Water
YES
***HW-800: 15 A, 115 V, 1 PHASE
Acid Waste
-
Hot Water
YES
Silver Recovery
-
Reagent Water
-
Medical Air
-
Laboratory Air
YES
Medical Vacuum
-
Laboratory Vacuum
YES
Oxygen
-
Fuel Gas
YES
Telephone
WALL MTD
ADP
-
Nitrous Oxide
-
Anesthesia Evac
-
Intercom
PART OF TELEPHONE
Radio
-
Notes:
Public Address -
Other
EMPTY CONDUIT*
Notes:
*TO ALLOW FOR DICTATION
VA Design Guide -- Veterinary Medical Unit