26 February 1993
Procedural Laboratory (Standard)
Design Standards
HEATING, VENTILATING AND AIR CONDITIONING
ARCHITECTURAL
Floor Area
240 NSF
Wall Finish
CMU (SC)
AC Load Lights
4.2 W/SF
Ceiling
PCP
Wainscot
-
AC Load Equipment
7.2 W/SF*
Ceiling Height
9'-0"
Base
ERF
Number of People
3
Slab Depression
-
Floor Finish
ERF
Noise Criteria
NC-40
Notes:
Lead Lining
-
Room Pressure
POSITIVE
Dry Bulb Temp Cooling (F)
78
72
Minimum Air Changes per Hour
15 (SA)
Minimum % Outside Air
100
YES
SPECIAL EQUIPMENT
YES**
H7-48 FUME HOOD
Steam
-
Relative Humidity - Cooling
50 %
Relative Humidity - Heating
30 %
Notes:
ELECTRICAL
*EXAM LIGHT INCLUDED IN EQUIPMENT LOAD
**H7: 875 CFM, 0.30" PD
Lighting
Power
General
70 FC, 3.5 W/SF*
General
540 W
Special
**
Special
***
Emergency
-
Emergency
-
Notes:
*FLUOR LAMPS COLOR CORRECTED
PLUMBING AND MEDICAL GASES
**(1) SURGICAL LIGHT, 1 HEAD
Sanitary Drain
YES
Cold Water
YES
***STRIP MOLD: 360 W; REFRIGERATOR: 1200 W; H7: 400W
Acid Waste
YES
Hot Water
YES
Silver Recovery
-
Reagent Water
-
Medical Air
-
Laboratory Air
YES
Medical Vacuum -
Laboratory Vacuum YES
Oxygen
-
Fuel Gas
YES
Telephone
WALL MTD
ADP
EMPTY CONDUIT
Nitrous Oxide
-
Anesthesia Evac
-
Intercom
PART OF TELEPHONE
Radio
-
Notes:
Public Address
-
Other
-
H7: LAB AIR, LAB VACUUM, FUEL GAS, COLD WATER, ACID WASTE
Notes:
VA Design Guide -- Veterinary Medical Unit
Guide Plate 5-8