26 February 1993
Incinerator Room
Design Standards
ARCHITECTURAL
HEATING, VENTILATING AND AIR CONDITIONING
Floor Area
200 NSF
Wall Finish
CMU (SC)
AC Load Lights
2.7 W/SF
Ceiling
PL
Wainscot
-
AC Load Equipment
1.5 W/SF*
Ceiling Height
10'-0" MIN*
Base
ERF
Number of People
-
Slab Depression
-
Floor Finish
ERF
Noise Criteria
NC-50
Notes:
Lead Lining
-
Room Pressure
(0)
*HEIGHT TO ACCOMMODATE EQUIPMENT SIZE
Dry Bulb Temp Cooling (F)
-
50
Minimum Air Changes per Hour
80 (MUA)**
Minimum % Outside Air
1600 CFM (MUA)**
YES
SPECIAL EQUIPMENT
Special Exhaust
-
INCINERATOR
Steam
-
Relative Humidity - Cooling
-%
Relative Humidity - Heating
-%
Notes:
ELECTRICAL
* PLUS INCINERATOR HEAT GAIN
**ADJUST VALUES TO COMPLY W/MANUFACTURERS RECOMMENDATIONS
Lighting
Power
INTERLOCK AUTO DAMPER WITH INCINERATOR, EXHAUST FAN, AND
General
10 FC, 0.5 W/SF
General
180 W
THERMOSTAT
Special
-
Special
-
Emergency
-
Emergency
-
Notes:
PLUMBING AND MEDICAL GASES
Sanitary Drain
-
Cold Water
-
Acid Waste
-
Hot Water
-
Silver Recovery
-
Reagent Water
-
Medical Air
-
Laboratory Air
-
Medical Vacuum
-
Laboratory Vacuum
-
Oxygen
-
Fuel Gas
YES
Telephone
-
ADP
-
Nitrous Oxide
-
Anesthesia Evac
-
Intercom
-
Radio
-
Notes:
Public Address
-
Other
-
Notes:
VA Design Guide -- Veterinary Medical Unit
Guide Plate 4-7