26 February 1993
Cold Room
Design Standards
ARCHITECTURAL
HEATING, VENTILATING AND AIR CONDITIONING
Floor Area
50 NSF
Wall Finish
-
AC Load Lights
-
Ceiling
-
Wainscot
-
AC Load Equipment
-
Ceiling Height
-
Base
-
Number of People
-
Slab Depression
YES
Floor Finish
-
Noise Criteria
-
Notes:
Lead Lining
-
Room Pressure
-
PREFABRICATED, SEE H-08-3 643-1
Dry Bulb Temp Cooling (F)
36
SEE H-08-1 SECTION 13062, AND H-08-3 CS 643-1
-
Minimum Air Changes per Hour
-
Minimum % Outside Air
-
50 CFM
SPECIAL EQUIPMENT
-
REFRIGERATION EQUIPMENT
Steam
-
Relative Humidity - Cooling
-%
Relative Humidity - Heating
-%
Notes:
ELECTRICAL
LOCATE CONDENSING UNIT AND REFRIGERANT PIPING ON PLANS
SEE H-08-4, SD 655.0, 655.1, 672.0, 672.1, AND 673.8
Lighting
Power
General
30 FC, 1.5 W/SF
General
180 W
Special
-
Special
*
Emergency
ALL
Emergency
ALL
Notes:
PLUMBING AND MEDICAL GASES
Sanitary Drain
-
Cold Water
-
*REFRIGERATION EQUIPMENT: 30 A, 208 V, 3 PHASE
Acid Waste
-
Hot Water
-
Silver Recovery
-
Reagent Water
-
Medical Air
-
Laboratory Air
-
Medical Vacuum
-
Laboratory Vacuum
-
Oxygen
-
Fuel Gas
-
Telephone
-
ADP
-
Nitrous Oxide
-
Anesthesia Evac
-
Intercom
-
Radio
-
Notes:
Public Address
-
Other
-
Notes:
VA Design Guide -- Veterinary Medical Unit
Guide Plate 4-5