26 February 1993
Locker, Toilet And Shower Room
Design Standards
ARCHITECTURAL
HEATING, VENTILATING AND AIR CONDITIONING
Floor Area
198 NSF
Wall Finish
CT
AC Load Lights
2.6 W/SF
Ceiling
PCP
Wainscot
-
AC Load Equipment
0.9 W/SF
Ceiling Height
9'-0"
Base
CT
Number of People
3
Slab Depression
-
Floor Finish
CT
Noise Criteria
NC-50
Notes:
Lead Lining
-
Room Pressure
NEGATIVE
Dry Bulb Temp Cooling (F)
78
78
Minimum Air Changes per Hour
10 (EA)
Minimum % Outside Air
100
YES
SPECIAL EQUIPMENT
-
NONE
Steam
-
Relative Humidity - Cooling
-%
Relative Humidity - Heating
-%
Notes:
ELECTRICAL
Lighting
Power
General
30 FC, 2.0 W/SF
General
360 W
Special
-
Special
-
Emergency
-
Emergency
-
Notes:
PLUMBING AND MEDICAL GASES
Sanitary Drain
YES
Cold Water
YES
Acid Waste
-
Hot Water
YES
Silver Recovery
-
Reagent Water
-
Medical Air
-
Laboratory Air
-
Medical Vacuum
-
Laboratory Vacuum
-
Oxygen
-
Fuel Gas
-
Telephone
-
ADP
-
Nitrous Oxide
-
Anesthesia Evac
-
Intercom
-
Radio
-
Notes:
Public Address
-
Other
-
Notes:
VA Design Guide -- Veterinary Medical Unit
Guide Plate 4-3