26 February 1993
Veterinarian Office
Design Standards
ARCHITECTURAL
HEATING, VENTILATING AND AIR CONDITIONING
Floor Area
120 NSF
Wall Finish
GWB-W
AC Load Lights
3.3 W/SF
Ceiling
AT
Wainscot
-
AC Load Equipment
2.3 W/SF
Ceiling Height
9'-0"
Base
RB
Number of People
2
Slab Depression
-
Floor Finish
CP
Noise Criteria
NC-40
Notes:
Lead Lining
-
Room Pressure
(0)
Dry Bulb Temp Cooling (F)
78
72
Minimum Air Changes per Hour
-
Minimum % Outside Air
100
YES
SPECIAL EQUIPMENT
-
NONE
Steam
-
Relative Humidity - Cooling
50 %
Relative Humidity - Heating
30 %
Notes:
ELECTRICAL
Lighting
Power
General
70 FC, 3.5 W/SF
General
1000 W*
Special
-
Special
-
Emergency
-
Emergency
-
Notes:
PLUMBING AND MEDICAL GASES
Sanitary Drain
-
Cold Water
-
*INCLUDE COMPUTER EQUIPMENT AT 60% PF
Acid Waste
-
Hot Water
-
Silver Recovery
-
Reagent Water
-
Medical Air
-
Laboratory Air
-
Medical Vacuum
-
Laboratory Vacuum
-
Oxygen
-
Fuel Gas
-
Telephone
DESK TYPE
ADP
-
Nitrous Oxide
-
Anesthesia Evac
-
Intercom
-
Radio
-
Notes:
Public Address
-
Other
-
Notes:
VA Design Guide -- Veterinary Medical Unit
Guide Plate 4-1