September 30, 1994
Design Standards
Soiled Receiving & Decontamination Area
ARCHITECTURAL
Ceiling
PL (SC)
Wainscot
-
Ceiling Height
2700 (9'-0")
Base
QT
Wall Finish
PL (SC)
Floor Finish
QT
Slab Depression
-
SPECIAL EQUIPMENT
VS-503: WASHER/STERILIZER
VS-210: STEAM STERILIZERS
HW-546: AUTOMATIC CART WASH
ELECTRICAL
Lighting
Power
General
30 FC - 2 W/SF
General
*
Special
-
Emergency
*
Notes: *VS-210: POWER DOOR - 15A, 120V; CONTROL - 1.0A, 120V
*VS-503: CONTROL - 10A, 120V; PUMP - 10A, 208V, 3 PH;
*HW-546: 20A, 480V, 3PH, 3 WIRE
ADP
-
Telephone
-
Radio
YES**
Intercom
EMPTY CONDUIT
Notes:
Public Address -
**CONNECT TO HOSPITAL SYSTEM
HEATING, VENTILATING AND AIR CONDITIONING
Dry Bulb Temp Cooling F
76
Relative Humidity/Cooling 50%
Minimum % Outside Air
100
Minimum Air Changes/Hr
10
YES
Room Pressure
NEGATIVE
Noise Criteria
NC-40
AC Load - Equipment
0.5574 W/SM
Steam
YES***
Number of People
3
Notes:
Special Exhaust
YES***
***VS EQUIP: SEE PG-08-6 FOR STEAM, HEAT GAIN, EXHAUST CAPACITY
HW-546: 1400 CFM EXH; 30-60 PSIG, 40 LB/HR STEAM
PLUMBING AND MEDICAL GASES
Cold Water
YES
Sanitary Drain
YES
Hot Water
YES
Reagent Grade Water
YES
Laboratory Air
YES
Laboratory Vacuum
-
Notes: ****FOR VS EQUIP
Other
SHOP AIR****
VA Design Guide -- Supply, Processing, & Distribution
Guide Plate 5-1