September 30, 1994
Design Standards
Lockers, Toilet, & Shower Room (Clean Area)
ARCHITECTURAL
Ceiling
PCP/AT
Wainscot
CT 1200 (4'-0")
Ceiling Height
2700 (9'-0")
Base
CT
Wall Finish
CT/GWB
Floor Finish
CT/VCT
Notes:
Slab Depression
-
SEPARATE FACILITIES FOR MEN AND WOMEN
ENCLOSED TOILET
ELECTRICAL
Lighting
Power
General
30 FC - 2 W/SF
General
400 W
Special
-
Emergency
-
Notes:
ADP
-
Telephone
-
Radio
-
Intercom
-
Notes:
Public Address -
HEATING, VENTILATING AND AIR CONDITIONING
Dry Bulb Temp Cooling F
76
Relative Humidity/Cooling -
Minimum % Outside Air
100
Minimum Air Changes/Hr
10
YES
Room Pressure
NEGATIVE
Noise Criteria
NC-40
AC Load - Equipment
0.0929 W/SM
Steam
-
Number of People
2
Notes:
-
PLUMBING AND MEDICAL GASES
Cold Water
YES
Sanitary Drain
YES
Hot Water
YES
Reagent Grade Water
-
Laboratory Air
-
Medical Air
-
Laboratory Vacuum
-
Medical Vacuum
-
Other
-
Oxygen
-
Notes:
VA Design Guide -- Supply, Processing, & Distribution
Guide Plate 4-3