September 30, 1994
Design Standards
Chief of SPD
ARCHITECTURAL
Ceiling
AT
Wainscot
-
Ceiling Height
2700 (9'-0")
Base
RB
Wall Finish
GWB/W/PL (SC)
Floor Finish
CP/VCT
Notes:
Slab Depression
-
SPECIAL EQUIPMENT
ELECTRICAL
Lighting
Power
General
70 FC - 4 W/SF
General
Special
-
Emergency
-
Notes:
ADP
YES
Telephone
YES
Radio
-
Intercom
-
Notes:
Public Address -
HEATING, VENTILATING AND AIR CONDITIONING
Dry Bulb Temp Cooling F
76
Relative Humidity/Cooling
50%
30%
Minimum % Outside Air
100
Minimum Air Changes/Hr
10
YES
Room Pressure
(0)
Noise Criteria
NC 40
AC Load - Equipment
0.4645 W/SM
Steam
-
Number of People
5
Notes:
-
PLUMBING AND MEDICAL GASES
Cold Water
-
Sanitary Drain
-
Hot Water
-
Reagent Grade Water
-
Laboratory Air
-
Medical Air
-
Laboratory Vacuum
-
Medical Vacuum
-
Other
-
Oxygen
-
Notes:
VA Design Guide -- Supply, Processing, & Distribution
Guide Plate 4-1a