Spinal Cord Injury Center Design Guide
July 1990 (Rev. Jan. 2004)
Combined Physical and Kinesiotherapy
Treatment Clinic 60 Beds
39
Function:
This space is intended to accommodate a wide variety of therapy techniques: manual (massage),
electronic (infrared, medcosonolator) and thermal (hot/cold packs.) SCI patients attend this clinic on a
daily basis for therapy, exercise and evaluation.
Space Requirement:
60 SCI Beds: 1496 NSF
Architectural:
Finish Code:
1-A
Floor Finish:
Base:
Vinyl
Wall Finish:
Gypsum Wallboard/Paint
Ceiling:
Acoustical Tile
Ceiling Height:
9'-6"
Noise (STC Rating):
30
Slab Depression:
None
Special Construction:
Wall-mounted pulleys require a reinforced wall with hardwood veneer plywood
surface, see Mspec #06200.
Hardware:
82
Doors:
2@3'-0" x 7'-0" wood or metal, upper half=laminated safety glass.
Windows:
Desirable, see PG-18-3, Topic 1, Codes and Standards.
HVAC:
Temperature:
Summer: 78@50%RH
Winter:
82@30%RH
Min. Air Changes/Hour: None (see HVAC Note 3)
Min. % Outside Air:
15%
Pressure:
(0)
% Filtration:
30%(PF)/85%(AF)
Noise Criteria:
40
A/C Loads:
Lights:
1050w
Equipment: 1250w
People:
1800w, sensible
3750w, latent
Electrical:
Lighting Levels:
Gen. Illum: 30fc
Emergency Power:
One Ceiling Light
Nurse Call
Equipment Table:
See Datasheet #38 for equipment (Column B).
Office of Facilities Management
207