Spinal Cord Injury Center Design Guide
July 1990 (Rev. Jan. 2004)
Multipurpose Recreational Therapy (Self-Directed) 21-A
Function:
This is the portion of the Recreation space that is available for self-directed activities such as discussion
groups or hobby clubs.
Space Requirement:
Included in space shown on Data Sheet #21.
Architectural:
Finish Code:
1-G
Floor Finish:
Base:
Vinyl
Wall Finish:
GWB/Vinyl Fabric Wallcover
Ceiling:
Acoustical Tile
Ceiling Height:
9'-0"
Noise (STC Rating):
45
Slab Depression:
None
Special Construction:
-
Hardware:
69
Doors:
4'-0" x 7'-0" wood or metal, optional glass view panel.
Windows:
Desirable
HVAC:
Temperature:
Summer: 72@50%RH
Winter:
82@30%RH
Min. Air Changes/Hour: None, (see HVAC Note 3)
Min. % Outside Air:
15%
Pressure:
(0)
% Filtration:
30%(PF)/85%(AF)
Noise Criteria:
40
A/C Loads:
Lights:
600w
Equipment: 600w
People:
800w, sensible
1040w, latent
Electrical:
Lighting Levels:
High: 50fc
Low: 30fc
Emergency Power:
-
Office of Facilities Management
126